Fisher valve positioner DVC6200 parameter setting method

February 8, 2025

Latest company news about Fisher valve positioner DVC6200 parameter setting method

DVC6200 and 475 communicator valve calibration debugging steps

1、Enter the interface, select HART

2, select online after enter

3、If there is an alarm signal, select YES and enter.

4, online drop-down menu select configure (configuration) and then press enter

5、Select calibration (calibration) menu and press enter.

6、Select autocalibration

7, warning menu select outofservice

8, select CONTINUE after enter select travelcontrol

9, the valve automatic calibration without operation, just wait until the following interface

10、Automatic calibration completed OK button to confirm

11, select OK

12, modified to become inservice state, the calibration is complete.

 

Positioner feedback debugging instructions

1, in the configure (configuration) menu select manualsetup

2, select the mode protection will inservice to OUTOFservice

3, choose to change the meter mode

4, select outofservice. enter and return

5、Warm reminder to choose OK

6、Select outputs in the manual setup to set the positioner feedback.

7、Select outputterminal

8、Select outputterminal

9、Select enable and enter

10, be sure to select send send after the completion of the feedback using the settings. Remember to change the valve back to inservice status.