(A) Valve automatic validation
1. After connecting the valve positioner to the hand manipulator, click on the field communication, select the bit number, click on the online, and select TRANSDUCE-T01-05.
2. After going in, select Configure/Setup, then select Detailed Setup, then select Change TB Mode. After going in, select Change Permitted and click OK.
3. Select Enable Man, click OK, select Exit, click OK.
4. Go back to the Detailed Setup interface, click Mode on the upper right, select Man, click OK, and then click Send.
5. Back to the Configure/Setup interface, select Calibration, select Auto Calibration, select YES, OK, wait, select Autocalibrate-Standard, click OK, the valve began to automatically validate. After the validation of the interface, select OK, appear Is Volume Booster or Graphite Packing Present? This interface select Graphite Packing only, click OK, the back of the selection of OK, the end.
(B) Valve manual give valve position
1. Select Device Diagnostics in the online interface, go in and click the mode on the upper right, select OOS and send the
2 Select Stroke Valve in Device Diagnostics interface, select YES, click OK, and then select Change to 'Not in Service' (TB to Manual) in the next interface, select yes, and click OK.
3. appear to manually give the valve position of the interface, select the first, (Step to Target) this point into it is possible to manually enter the desired valve position, the second is 10% to give, the third is 1% to give, want to end the click on the fourth (Exit Stroke Valve) click on OK, select Set 'In Service Select Set 'In Service' and click OK to finish.